Temperature ControlleriB6 / iB125.Parameter Characteristics
5.1 Introduction
This section contains information about every configuration parameter, including valid ranges,
control mode(s) to which the parameter applies and interactions among parameters.
For an overview of configuration menus and parameters refer to Section 3.7.
5.2 Input Parameters
5.2.1 Introduction
You can use the Input Config menu to specify for the selected zone(s):
• bias (if any) to be applied to the input,
• setpoint range, and
• input type
5.2.2 Input Parameters and Settings
Name Applies to Range/
Choices
Default Description & Interactions
Selected Zones
All Zones
Closed Loop Control
Open Loop Control
Bias
–55 to 55 °C
–100 to 100 °F
0° Number of degrees that will be
added to or subtracted from the
measured process value before it
is displayed
Low Setpoint
Limit
0 to 537 °C
32 to 999 °F
0 °C
32 °F
Lowest and highest values
that can be entered as setpoint
(before bias is applied); also
limits configurable range of boost
setpoint and standby setpoint
High Setpoint
Limit
0 to 537 °C
32 to 999 °F
537 °C
999 °F
Input Type
J Thermo
K Thermo
Input type
specified
when unit
was ordered
Switching to input type that does
not match the type specified
when the unit was ordered can
cause small errors (1-5 degrees)
in temperature measurements